SPHINX 104-360/2. Công tắc cảm biến hiện diện, 360 độ, gắn trần chìm, 2 kênh.

  • Liên hệ
  • Germany
  • 12 Months
  • SPHINX 104-360 - passive infrared sensor and light metering provides features to control lighting automatically, turn on the lights when it gets dark and have someone turn the lights off after people leave a time or when the light was enough. The device detects the person based on the slightest movement.

Features of SPHINX 104-360 :

  • Presence detector (PIR)
  • 1 channel
  • Flush-mounted installation
  • Lighting control with adjustable light threshold value and adjustable switch-off delay
  • Teach-in of current brightness value possible via remote control
  • Additional pulse function can be selected for combination with staircase timer (ELPA), building automation or PLC
  • Master/slave function: Up to ten detectors to expand detection area
  • Test function for checking detection area
  • Zero-cross switching
  • Automatic lighting control based on presence and brightness
  • Detection area can be limited using three enclosed segments
  • Mixed light measurement suitable for the control of fluorescent, incandescent and halogen lamps
  • Instant start-up possible via factory preset
  • Push-button or switch options for manual switching
  • Screwless terminals for quick installation

sphinx_104_360_1

 

sphinx_104_360_2

 

 

Operating voltage 230 VAC
Frequency 50 – 60 Hz
Stand-by consumption ~1 W
Light measurement Mixed light measurement
Number of channels 1
Type of contact NO contact
Colour White
Switching output Light
nstallation type Ceiling installation
Setting range brightness 10 – 2000 lx
Switching capacity 8 A at 230 V AC, cos φ = 1
Detection angle 360°
Installation height 2.5 – 3.5 m
Light switch-off delay  1 s-20 min
Incandescent/halogen lamp load 1800 W
Fluorescent lamp load (conventional) not corrected 900 VA
Fluorescent lamp load (conventional) parallel-corrected 400 VA 42 µF
Fluorescent lamp load (conventional) series-corrected 900 VA
Fluorescent lamp load (conventional) lead-lag circuit 900 VA
Fluorescent lamp load (electronic ballast) 400 VA
Energy saving lamps

4 x 7 W, 3 x 11 W, 3 x 15 W,

3 x 20 W, 3 x 23 W

LED lamp < 2 W 25 W
LED lamp 2-8 W 90 W
Lamps Incandescent/halogen lamps, fluorescent lamps, Energy saving lamps, LEDs
Detection range 133 m² (ø 13 m | 360°)
Remote controlled có
Ambient temperature -10°C ... 55°C
Protection class II
Type of protection IP 41